Valve con­trol – HE 5711 (stan­dard rail)

Small control unit with attractive price/performance ratio

Control of up to 8 valves

2 operating modes: continuous operation or cyclic operation

Function display (LEDs) for all valves

Automatic valve detection

Attractive price/performance ratio

 

 

 

Produkt anfragen

 

 

Valve con­trol for all vol­tage ran­ges

The micro­con­trol­ler-based valve con­trol HE 5711 is used for the cycle con­trol of elec­tro­ma­gne­tic val­ves in indus­trial dust fil­ter sys­tems. The fle­xi­ble design con­cept enables use as a stan­dard rail ver­sion or as a con­trol unit in a dust-tight Makro­lon housing with ATEX Zone 22 appr­oval. The con­trol­ler auto­ma­ti­cally detects the num­ber of solenoid val­ves con­nec­ted. The clea­ning pro­ces­ses are time-con­trol­led – for this pur­pose, the pulse and pause times are set via poten­tio­me­ters. After the end of nor­mal clea­ning, the con­trol sys­tem can carry out post-clea­ning if desi­red.

Applications

Bunker top filter, industrial vacuum cleaner

Break time regulation

Technical data

HE 5711
Sup­ply vol­tage100 – 240 V AC, 50 – 60 Hz
Option: 24 V DC ± 10% [SELV]
Power con­sump­tion30 VA, own power con­sump­tion about 3 W
LEDs4 × for valve con­trol, red
RUN, green
PULSE, yel­low
PAUSE, yel­low
TEST, green
Con­trol ele­mentsBut­ton TEST: the next valve is actua­ted
PULSE, set­ting the pulse period
Poten­tio­me­ter from 0.02 and 1.2 seconds

PAUSE, set­ting the pause time
Poten­tio­me­ter from 1 and 270 seconds

CYCLES: set­ting the cycles
Rotary coded switch 0 - 9; 0 deac­ti­va­tes the func­tion
InputsSTART, Post-clea­ning
Valve out­puts8
Valve vol­tage 24 V DC / 1A, short-cir­cuit proof
Valve cur­rentSpring ter­mi­nals for 1.5 mm²
EMVDIN-EN 61000-6-2 (inter­fe­rence immu­nity in the indus­trial sec­tor)
DIN-EN 61000-6-4 (inter­fe­rence emis­si­ons in the indus­trial sec­tor)
Explo­sion pro­tec­tionOnly with the ver­sion in the dust-tight Makro­lon housing
Valve con­trol – HE 5711 (Housing)
HousingCon­s­truc­tion on a stan­dar­di­sed rail sup­port; 165 mm × 111 mm (W × H)

Errors and omis­si­ons excepted

Downloads

Ope­ra­ting Ins­truc­tions HE 5711 – Eng­lish

Ope­ra­ting Ins­truc­tions HE 5711 – Ger­man

Data sheet HE 5711 – Ger­man

EPLAN macros HE 5710 / HE 5711

    captcha

    ACHTUNG: Zum Absenden des Formulars muss der rechtliche Hinweis mit einem Häkchen bestätigt werden.